| Power contactor, AC-3 80 A, 37 kW / 400 V 2 NO + 2 NC, 220 V AC, 50 Hz 240 V, 60Hz, 3-pole Size S2, screw terminals |
| Product brand name | SIRIUS |
| Product designation | Power contactor |
| Product type designation | 3RT2 |
| General technical data |
| Size of contactor | S2 |
| Product extension | |
| function module for communication | No |
| Auxiliary switch | No |
| Surge voltage resistance | |
| of main circuit rated value | 6 kV |
| of auxiliary circuit rated value | 6 kV |
| maximum permissible voltage for safe isolation | |
| between coil and main contacts acc. to EN 60947-1 | 400 V |
| Protection class IP | |
| on the front | IP20 |
| of the terminal | IP00 |
| Shock resistance at rectangular impulse | |
| at AC | 9.8g / 5 ms, 6.5g / 10 ms |
| Shock resistance with sine pulse | |
| at AC | 15.3g / 5 ms, 10.1g / 10 ms |
| Mechanical service life (switching cycles) | |
| of contactor typical | 10 000 000 |
| of the contactor with added electronics-compatible auxiliary switch block typical | 5 000 000 |
| of the contactor with added auxiliary switch block typical | 10 000 000 |
| Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750 | K |
| Reference code acc. to DIN EN 81346-2 | Q |
| Ambient conditions |
| Installation altitude at height above sea level | |
| maximum | 2 000 m |
| Main circuit |
| Number of poles for main current circuit | 3 |
| Number of NO contacts for main contacts | 3 |
| Operating voltage | |
| at AC-3 rated value maximum | 690 V |
| Operating current | |
| at AC-1 at 400 V | |
| — at ambient temperature 40 °C rated value | 90 A |
| at AC-1 | |
| — up to 690 V at ambient temperature 40 °C rated value | 90 A |
| — up to 690 V at ambient temperature 60 °C rated value | 80 A |
| at AC-2 at 400 V rated value | 80 A |
| at AC-3 | |
| — at 400 V rated value | 80 A |
| — at 500 V rated value | 80 A |
| — at 690 V rated value | 58 A |
| at AC-4 at 400 V rated value | 55 A |
| at AC-5a up to 690 V rated value | 79.2 A |
| at AC-5b up to 400 V rated value | 66.4 A |
| at AC-6a | |
| — up to 230 V at current peak n=20 rated value | 70 A |
| — up to 400 V at current peak n=20 rated value | 70 A |
| — up to 500 V at current peak n=20 rated value | 70 A |
| — up to 690 V at current peak n=20 rated value | 58 A |
| at AC-6a | |
| — up to 230 V at current peak n=30 rated value | 46.7 A |
| — up to 400 V at current peak n=30 rated value | 46.7 A |
| — up to 500 V at current peak n=30 rated value | 46.7 A |
| — up to 690 V at current peak n=30 rated value | 46.7 A |
| Connectable conductor cross-section in main circuit at AC-1 | |
| at 60 °C minimum permissible | 25 mm² |
| at 40 °C minimum permissible | 35 mm² |
| Operating current for approx. 200000 operating cycles at AC-4 | |
| at 400 V rated value | 30 A |
| at 690 V rated value | 24 A |
| Operating current | |
| at 1 current path at DC-1 | |
| — at 24 V rated value | 55 A |
| — at 110 V rated value | 4.5 A |
| — at 220 V rated value | 1 A |
| — at 440 V rated value | 0.4 A |
| — at 600 V rated value | 0.25 A |
| with 2 current paths in series at DC-1 | |
| — at 24 V rated value | 55 A |
| — at 110 V rated value | 45 A |
| — at 220 V rated value | 5 A |
| — at 440 V rated value | 1 A |
| — at 600 V rated value | 0.8 A |
| with 3 current paths in series at DC-1 | |
| — at 24 V rated value | 55 A |
| — at 110 V rated value | 55 A |
| — at 220 V rated value | 45 A |
| — at 440 V rated value | 2.9 A |
| — at 600 V rated value | 1.4 A |
| Operating current | |
| at 1 current path at DC-3 at DC-5 | |
| — at 24 V rated value | 35 A |
| — at 110 V rated value | 2.5 A |
| — at 220 V rated value | 1 A |
| — at 440 V rated value | 0.1 A |
| — at 600 V rated value | 0.06 A |
| with 2 current paths in series at DC-3 at DC-5 | |
| — at 24 V rated value | 55 A |
| — at 110 V rated value | 25 A |
| — at 220 V rated value | 5 A |
| — at 440 V rated value | 0.27 A |
| — at 600 V rated value | 0.16 A |
| with 3 current paths in series at DC-3 at DC-5 | |
| — at 24 V rated value | 55 A |
| — at 110 V rated value | 55 A |
| — at 220 V rated value | 25 A |
| — at 440 V rated value | 0.6 A |
| — at 600 V rated value | 0.35 A |
| Operating power | |
| at AC-1 | |
| — at 230 V rated value | 34 kW |
| — at 230 V at 60 °C rated value | 28 kW |
| — at 400 V rated value | 59 kW |
| — at 400 V at 60 °C rated value | 49 kW |
| — at 690 V rated value | 102 kW |
| — at 690 V at 60 °C rated value | 85 kW |
| at AC-2 at 400 V rated value | 37 kW |
| at AC-3 | |
| — at 230 V rated value | 22 kW |
| — at 400 V rated value | 37 kW |
| — at 500 V rated value | 37 kW |
| — at 690 V rated value | 45 kW |
| Operating power for approx. 200000 operating cycles at AC-4 | |
| at 400 V rated value | 15.8 kW |
| at 690 V rated value | 21.8 kW |
| Thermal short-time current limited to 10 s | 640 A |
| Power loss [W] at AC-3 at 400 V for rated value of the operating current per conductor | 5.7 W |
| No-load switching frequency | |
| at AC | 5 000 1/h |
| Operating frequency | |
| at AC-1 maximum | 700 1/h |
| at AC-2 maximum | 350 1/h |
| at AC-3 maximum | 500 1/h |
| at AC-4 maximum | 150 1/h |
| Control circuit/ Control |
| Type of voltage of the control supply voltage | AC |
| Control supply voltage at AC | |
| at 50 Hz rated value | 220 V |
| at 60 Hz rated value | 240 V |
| Operating range factor control supply voltage rated value of magnet coil at AC | |
| at 50 Hz | 0.8 ... 1.1 |
| at 60 Hz | 0.8 ... 1.1 |
| Apparent pick-up power of magnet coil at AC | |
| at 50 Hz | 212 V·A |
| at 60 Hz | 188 V·A |
| Inductive power factor with closing power of the coil | |
| at 50 Hz | 0.69 |
| at 60 Hz | 0.65 |
| Apparent holding power of magnet coil at AC | |
| at 50 Hz | 18.5 V·A |
| at 60 Hz | 16.5 V·A |
| Inductive power factor with the holding power of the coil | |
| at 50 Hz | 0.36 |
| at 60 Hz | 0.39 |
| Closing delay | |
| at AC | 10 ... 80 ms |
| Opening delay | |
| at AC | 10 ... 18 ms |
| Arcing time | 10 ... 20 ms |
| Control version of the switch operating mechanism | Standard A1 - A2 |
| Auxiliary circuit |
| Number of NC contacts for auxiliary contacts | |
| instantaneous contact | 2 |
| Number of NO contacts for auxiliary contacts | |
| instantaneous contact | 2 |
| Operating current at AC-12 maximum | 10 A |
| Operating current at AC-15 | |
| at 230 V rated value | 6 A |
| at 400 V rated value | 3 A |
| at 500 V rated value | 2 A |
| at 690 V rated value | 1 A |
| Operating current at DC-12 | |
| at 24 V rated value | 10 A |
| at 48 V rated value | 6 A |
| at 60 V rated value | 6 A |
| at 110 V rated value | 3 A |
| at 125 V rated value | 2 A |
| at 220 V rated value | 1 A |
| at 600 V rated value | 0.15 A |
| Operating current at DC-13 | |
| at 24 V rated value | 6 A |
| at 48 V rated value | 2 A |
| at 60 V rated value | 2 A |
| at 110 V rated value | 1 A |
| at 125 V rated value | 0.9 A |
| at 220 V rated value | 0.3 A |
| at 600 V rated value | 0.1 A |
| Contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
| UL/CSA ratings |
| Full-load current (FLA) for three-phase AC motor | |
| at 480 V rated value | 65 A |
| at 600 V rated value | 62 A |
| Yielded mechanical performance [hp] | |
| for single-phase AC motor | |
| — at 110/120 V rated value | 5 hp |
| — at 230 V rated value | 15 hp |
| for three-phase AC motor | |
| — at 200/208 V rated value | 20 hp |
| — at 220/230 V rated value | 25 hp |
| — at 460/480 V rated value | 50 hp |
| — at 575/600 V rated value | 60 hp |
| Contact rating of auxiliary contacts according to UL | A600 / Q600 |
| Short-circuit protection |
| Design of the fuse link | |
| for short-circuit protection of the main circuit | |
| — with type of coordination 1 required | gG: 250 A (690 V, 100 kA), aM: 160 A (690 V, 100 kA), BS88: 200 A (415 V, 80 kA) |
| — with type of assignment 2 required | gG: 160A (690V,100kA), aM: 80A (690V,100kA), BS88: 125A (415V,80kA) |
| for short-circuit protection of the auxiliary switch required | gG: 10 A (500 V, 1 kA) |
| Installation/ mounting/ dimensions |
| Mounting position | +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface |
| Mounting type | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715 |
| Side-by-side mounting | Yes |
| Height | 114 mm |
| Width | 55 mm |
| Depth | 174 mm |
| Required spacing | |
| with side-by-side mounting | |
| — forwards | 10 mm |
| — upwards | 10 mm |
| — downwards | 10 mm |
| — at the side | 0 mm |
| for grounded parts | |
| — forwards | 10 mm |
| — upwards | 10 mm |
| — at the side | 6 mm |
| — downwards | 10 mm |
| for live parts | |
| — forwards | 10 mm |
| — upwards | 10 mm |
| — downwards | 10 mm |
| — at the side | 6 mm |
| Connections/Terminals |
| Type of electrical connection | |
| for main current circuit | screw-type terminals |
| for auxiliary and control current circuit | screw-type terminals |
| Type of connectable conductor cross-sections | |
| for main contacts | |
| — single or multi-stranded | 2x (1 ... 35 mm²), 1x (1 ... 50 mm²) |
| — finely stranded with core end processing | 2x (1 ... 25 mm²), 1x (1 ... 35 mm²) |
| at AWG conductors for main contacts | 2x (18 ... 2), 1x (18 ... 1) |
| Connectable conductor cross-section for main contacts | |
| finely stranded with core end processing | 1 ... 35 mm² |
| Connectable conductor cross-section for auxiliary contacts | |
| single or multi-stranded | 0.5 ... 2.5 mm² |
| finely stranded with core end processing | 0.5 ... 2.5 mm² |
| Type of connectable conductor cross-sections | |
| for auxiliary contacts | |
| — single or multi-stranded | 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²) |
| — finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| at AWG conductors for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14) |
| AWG number as coded connectable conductor cross section | |
| for main contacts | 18 ... 1 |
| for auxiliary contacts | 20 ... 14 |
| Safety related data |
| B10 value | |
| with high demand rate acc. to SN 31920 | 1 000 000 |
| Proportion of dangerous failures | |
| with low demand rate acc. to SN 31920 | 40 % |
| with high demand rate acc. to SN 31920 | 73 % |
| Failure rate [FIT] | |
| with low demand rate acc. to SN 31920 | 100 FIT |
| Product function | |
| Mirror contact acc. to IEC 60947-4-1 | Yes |
| positively driven operation acc. to IEC 60947-5-1 | No |
| T1 value for proof test interval or service life acc. to IEC 61508 | 20 y |
| Protection against electrical shock | finger-safe when touched vertically from front acc. to IEC 60529 |